The power adopts advantaged SPWM IGBT high-frequency inverter technology, internal structure is AC-DC-AC, thoroughly eliminate the network interference, output wave forms are pure. It has the following features: wide range of constant-voltage and constant-frequency, high precision, light weight, small capacity, output transformer with apartheid, with the good with a high quality uninterrupted power supply system.
Single phase type
● Input voltage: 130~280V
● Input frequency: 30~70Hz
● Output voltage: 220±1%
● Output frequency: 50Hz±0.01%
● Wave distortion: <1%
● Isolation transformer output, safe and credible
● Auto-protection and alarm for output over-voltage, over current, overheat, short circuit
Efficiency reach above 90% ,widely applicable load,for nasty, capacitive resistance,any combination of the load
Technic parameter
| Model | 11005 | 11010 | 11030 | 11050 | 11100 | 31150 | 31200 | 313000 | 31450 | 311000 | ||||||
| Capacity(VA) | 500 | 1K | 3K | 5K | 10K | 15K | 20K | 30K | 45K | 100K | ||||||
| Output currency | 2.1 | 4.2 | 12 | 21 | 42 | 63 | 84 | 125 | 188 | 420 | ||||||
| Circuit model | IGBT/SPWM pulse width adjustment mode | |||||||||||||||
| AC Input | Voltage | 130V-280V | 265V-495V | |||||||||||||
| Frequency | 30-70Hz | |||||||||||||||
| Phase | single phase | three phase four wire | ||||||||||||||
| AC output voltage | 220V±1% | |||||||||||||||
| Output frequency | 50Hz/60Hz | |||||||||||||||
| frequency stability | ≤±0.01% | |||||||||||||||
| Voltage stability | ≤1% | |||||||||||||||
| Wave distortion | ≤2% | |||||||||||||||
| Reaction time | ≤2mS | |||||||||||||||
| DPI (dots per inch) | frequency meter | 0.1Hz | ||||||||||||||
| Voltage meter | 0.1V | |||||||||||||||
| Current meter | 0. 1A | |||||||||||||||
| Power meter | 0.1W | |||||||||||||||
| Efficiency | efficiency more than 90% ,be suit for wide-load, can be for the inductive, capacitive, resistive, and any mixed loads. | |||||||||||||||
| Protection function | The importation of non-fuse switch, without output fuse switch, the electronic circuit to detect over-voltage Express .Over voltage, over current, over temperature, over load, short circuit, and automatic alarm. | |||||||||||||||
| Insulation reactance | 500Vdc 20MΩ | |||||||||||||||
| Pressure endurance insulation | 1500Vac/5mA/1min | |||||||||||||||
| Cooling model | Compulsive fan cooling | |||||||||||||||
| Working temperature | -10℃-45℃ | |||||||||||||||
| Relative humidity | 0-90%(No condensing) | |||||||||||||||
| Altitude | 1500meters | |||||||||||||||
| Dimension (W×L×H)mm | 410*440*135 | 460*440*220 | 560*350*600 | 660*400*700 | 830*450*1100 | 1160*520* 1370 | ||||||||||
Three phase output type
● Input voltage: 265~495V
● Input frequency: 30~70Hz
● Output voltage: 380V±1%
● Output frequency: 50Hz±0.01%
● Wave distortion: <1%
● Isolation transformer output, safe and credible
● Auto-protection and alarm for output over voltage, over current, overheat, short circuit
● Efficiency reaches above 90%, widely applicable load, for nasty, capacitive resistance, any combination of the load
● Dynamic quick, when load changes in 0 - 100%, stationary response time<0.1S
Technic parameter
|
Model |
13100 |
33150 |
33300 |
33450 |
33600 |
331000 |
333000 |
336000 |
338000 |
3316000 |
||
|
Capacity(KVA) |
10 |
15 |
20 |
45 |
60 |
100 |
300 |
600 |
800 |
1600 |
||
|
Output currency(A) |
13.8 |
20.8 |
42 |
63 |
84 |
138 |
400 |
800 |
1050 |
2100 |
||
|
Circuit model |
IGBT/SPWM pulse width adjustment mode |
|||||||||||
|
AC Input |
Voltage |
130V-280V |
265V-495V |
|||||||||
|
Frequency |
30-70Hz |
|||||||||||
|
Phase |
Single phase |
three phase four wire |
||||||||||
|
AC output voltage |
380V±1% |
|||||||||||
|
Output frequency |
50HZ |
|||||||||||
|
frequency stability |
≤±0.01% |
|||||||||||
|
Voltage stability |
≤3% |
|||||||||||
|
Reaction time |
≤2mS |
|||||||||||
|
Wave distortion |
≤2% |
|||||||||||
|
Frequency meter |
0.1Hz |
|||||||||||
|
Voltage meter |
0.1V |
|||||||||||
|
Current meter |
0. 1A |
|||||||||||
|
Power meter |
0.1W |
|||||||||||
|
Efficiency |
efficiency more than 90% ,be suit for wide-load, can be for the inductive, capacitive, resistive, and any mixed loads. |
|||||||||||
|
Protection function |
The importation of non-fuse switch, without output fuse switch, the electronic circuit to detect over-voltage Express .Over voltage, over current, over temperature, over load, short circuit, and automatic alarm. |
|||||||||||
|
Insulation reactance |
500Vdc 20MΩ |
|||||||||||
|
Pressure endurance insulation |
1500Vac/5mA/1min |
|||||||||||
|
Cooling model |
Compulsive fan cooling |
|||||||||||
|
Working temperature |
-10℃-45℃ |
|||||||||||
|
Relative humidity |
0-90%(No condensing) |
|||||||||||
|
Altitude |
1500meters |
|||||||||||
|
Dimension (W×L×H)mm |
410*440*135 |
460*440*220 |
560*350*600 |
660*400*700 |
1000*600*2080 |
1000*4000*2080 |
||||||
|
Model |
332500 |
3350000 |
33100000 |
|||
|
Capacity(KVA) |
2500 |
5000 |
10000 |
|||
|
Input |
Voltage |
265V-495V 3phase 4wires or 3phase 5wires |
||||
|
Frequency |
30~70Hz |
|||||
|
Power Factor |
≥0.90 |
|||||
|
Output |
Voltage |
3phase 4 wires ,voltage380vac |
||||
|
Frequency |
50Hz |
|||||
|
Frequency Stability |
≤0.01%(0-100% when load are changing,output frequency are not changing ) |
|||||
|
Load Stability |
≤3%(100% pure resistance load) |
|||||
|
Overload Ability |
110% 1hour,150% 10minutes |
|||||
|
Wave Distortion |
Pure sine wave,THD≤3% |
|||||
|
Efficiency |
≥90%(100% loads) |
|||||
|
Display |
Input/output voltage/ frequency,3phase phase voltage/current,active power .working time.history error etc. |
|||||
|
Control mode |
IGBT/SPWM Pulse width adjustment mode |
|||||
|
Protection Class |
IP54 |
|||||
|
Insulation Reactance |
>2MΩ |
|||||
|
Pressure endurance Insulation |
1800Vac/5Ma/1minute |
|||||
|
Noise Level |
50dBA @1meter |
|||||
|
Cooling Model |
Converter: heat pipe cooling. Transformer: Compulsive fan cooling |
|||||
|
Protection Function |
The output power supply have perfect protection function of over voltage, over current, short circuit, converter overheat . Consider the different control of the ship's electricity load, when the output load capacity reach the set value,will alarm, so as to control the electricity load |
|||||
|
Environment |
-10℃~+50℃ and 0~90% |
|||||
|
Dimension |
1500*6000*2080 |
2000*8000*2080 |
2000*8000*2080+2000*8000*2080 |
|||
|
Weight |
8T |
12T |
20T |
|||
No.220 Huayuan Road Jinan city China