1500kw and 3000kw bi-directional inverter
System Diagram
1.Main circuit adopt USA TI company DSP chip and IGBT from Mitsubishi,driving
protection is from Japan Mitsubishi chip,the part of off-grid output adopt isolation transformer,safe and reliable.
2.With SPWM pulse width modulation technology,pure sine wave output,power factor
approaches 1,low current harmonic content
3.MPPT(Maximum Power Point Tracking)Technology
4.Inverting current close-cycle control,power to control and adjustable
5.With wide input voltage range to adapt to the needs of different occasions
6.Have a full range scheme of power protection and perfect self-detection and self- protection function.When there’s something wrong with the system,it will automatically
stop working.
7.Close circuit structure, the maximum efficiency> 94%
Technic parameter
|
Type |
XNSGA-1500KS |
XNSGA-3000KS |
|
Isolation |
Low frequency transformer isolation |
|
|
Max. DC input power |
1550KWp |
3200KWp |
|
Max. DC input |
900Vdc |
|
|
Input voltage range |
450Vdc~800Vdc |
|
|
Nominal AC output power |
1500KW |
3000KW |
|
THD of AC current |
<3%(nominal power) |
|
|
Power factor |
>0.99(nominal power) |
|
|
Max. Efficiency |
95% |
|
|
Nominal AC output voltage |
400Vac±15% |
|
|
Nominal AC |
50Hz±1% |
|
|
Automatic restart time |
2min(adjustable) |
|
|
Protection |
Input reverse connection protection,output short circuit protection, overheat protection,overload protection |
|
|
Comm. interfaces |
Ethernet |
|
|
Operating Temp. |
-20℃~+50℃ |
|
|
Relative humidity |
0~95% |
|
|
Altitude(m) |
≤6000meters(Over 2000 meters to reduce |
|
|
Cooling method |
Controlled forced-air cool |
|
|
Noise |
≤60dB |
|
|
Protection degree |
IP20(indoor) |
|
XYH-PCS series Bi-directional storage Inverter modular type
XYH series Bi-directional storage Inverter is the key equipment for energy exchange between energy storage battery components and power grid. It can accept power grid dispatching instructions, realize charging and discharge management of energy storage battery, and realize power grid peak shaving / frequency modulation function. It can monitor the real-time characteristics of load and realize peak shaving and valley filling. At the same time, it can provide reactive power support, make up for voltage defects, control power quality and so on to ensure the stable operation of power grid system. It has the ability to resist short-term impact and can carry completely unbalanced load to realize smooth power supply.
Economical and efficient
Safe and reliable
Intelligent and friendly
Technic parameter
|
Parameter table |
XYH-PCS/500 |
XYH-PCS/630 |
|
DC side parameters |
||
|
Maximum DC power(kW) |
560kW |
693kW |
|
Maximum voltage of DC bus (V) |
1000V |
1000V |
|
Maximum current at DC side (A) |
948A |
1195A |
|
DC voltage operating range (V) |
550~1000V |
550~1000V |
|
DC voltage ripple coefficient (%) |
<2% |
<2% |
|
AC side parameters (grid connection) |
||
|
Rated power (kW) |
500kW |
630kW |
|
Maximum output power (kW) |
550kW |
693kW |
|
Rated output current |
760A |
957A |
|
Maximum output current |
912A |
1148A |
|
Rated grid voltage (V) |
Three phase three wire |
Three phase three wire |
|
Allowable grid voltage (V) |
-15%~10% or 323V-418V |
-15%~10% or 323V-418V |
|
Rated grid frequency (Hz) |
50Hz/60Hz(±2Hz) |
50Hz/60Hz(±2Hz) |
|
Current total harmonic distortion rate (%) |
<3%(Rated power) |
<3%(Rated power) |
|
Power factor |
>0.98(leading or lagging) |
>0.98(leading or lagging) |
|
Charge discharge conversion time (ms) |
<20ms |
<20ms |
|
AC side (off grid) |
||
|
Voltage unbalance (V) |
380V±3% |
380V±3% |
|
Voltage unbalance (%) |
<2%, short-term 4% |
<2%, short-term 4% |
|
Voltage total harmonic distortion rate (%) |
<3%( Linear load) |
<3%( Linear load) |
|
Maximum reachable efficiency (Hz) |
50Hz/60Hz |
50Hz/60Hz |
|
System |
||
|
Maximum reachable efficiency |
99% |
99% |
|
Overload capacity |
1.1 times long term, |
1.1 times long term |
|
Allowable ambient temperature (℃) |
-25 ℃~+65 ℃(Derating is required when the temperature exceeds 55 ℃) |
-25 ℃~+65 ℃(Derating is required when the temperature exceeds 55 ℃) |
|
Allowable relative humidity (%) |
0~95%,No condensation |
0~95%,No condensation |
|
Maximum working altitude |
5000 m (>3000 m Derating) |
5000 m (>3000 m Derating) |
|
Overall size |
693*1590*601 |
693*1590*601 |
|
Machine weight (kg) |
550kg |
550kg |
|
Degree of protection |
IP20 |
IP20 |
|
Cooling mode |
Forced air cooling |
Forced air cooling |
|
Display and communication |
||
|
Communication interface |
RS485, Ethernet, EtherCAT,CAN |
RS485, Ethernet, EtherCAT,CAN |
|
Interface |
HMI |
HMI |
|
Communication protocol |
MODBUS-RTU /MODBUS-TCP/CAN2.0B |
MODBUS-RTU /MODBUS-TCP/CAN2.0B |
XYH storage bi-directional inverter
Bi-directional inverter can not only convert the DC power into AC power,but also can invert the AC power to DC power.Bi- directional inverter mainly control the battery’s charging and discharging,at same time it is the core control equipment.Bi-directional inverter can apply in the grid ties power system which has the requirement of power storage function.The power storage system is for the the emerging load or important load charging.It can combine with the string inverter and then construct the separated PV power system.
Bi-directional inverter charged by batteries ,convert the DC power into AC power.Constructing the grid at the basis of the AC general line.String grid inverter can automatically test the solar battery array with enough power or not.Testing the grid whether meet the need of grid power.When meeting the need can go into the grid power mode,feeding power to the AC general line.,then the work of starting the system was completed.When normally operating .Bi-grid inverter will test the power using of the load .The power feeding to the grid from string grid inverter firstly for the load charging.If there is rest power ,BI-grid inverter will convert it into DC power and charge the battery.If the power feeding to the grid is not enough for the load,Bi-grid inverter will convert the DC power supplied by battery into AC power and feed into the AC general line for the using of the load.
Technic parameter
|
Type |
XSX10KS |
XSX20KS |
XSX50KS |
XSX100KS |
XSX250KS |
XSX500KS |
XSX1000KS |
||
|
AC side parameter |
|||||||||
|
Rated capacity |
10kW |
20kW |
50 kW |
100 kW |
250kW |
500Kw |
1000Kw |
||
|
Overload |
11kW |
22 kW |
55 kW |
110 kW |
275kW |
550kW |
1100kW |
||
|
On-grid charging mode |
|||||||||
|
Rated grid voltage |
400 Vac |
||||||||
|
Grid voltage range |
330~460Vac |
||||||||
|
Grid frequency |
50Hz/60Hz |
||||||||
|
Total harmonic distortion(THD) |
<3% |
||||||||
|
Power factor |
≥0.99 |
||||||||
|
off-grid mode |
|||||||||
|
Rated output voltage |
400 Vac |
||||||||
|
Output voltage accuracy |
<3% |
||||||||
|
Output frequency |
50Hz/60Hz |
||||||||
|
Output overvoltage |
>460 Vac |
||||||||
|
Output under-voltage |
<330 Vac |
||||||||
|
DC voltage range |
|||||||||
|
Max DC power |
11kW |
22 kW |
55 kW |
110 kW |
275kW |
550kW |
1100kW |
||
|
DC voltage range |
450-1000Vdc |
||||||||
|
Max DC current |
25A |
50A |
122A |
244A |
611A |
1320A |
2640A |
||
|
DC current ripple |
<5% |
||||||||
|
System |
|||||||||
|
Max efficiency |
96.6% |
||||||||
|
Temperature |
-25~+60°C |
||||||||
|
Humidity |
0~95%,non condensing |
||||||||
|
Noise |
<50dB |
||||||||
|
Protection |
Polarity inverse,short circuit,island efficiency.overheat,overload.ground fault protection |
||||||||
|
Cooling method |
Forced cooling |
||||||||
|
Protect degree |
IP20 |
||||||||
|
Indication |
Touching screen |
||||||||
|
Communication |
RS485(MODBUS protocol) |
||||||||
|
W×D×H(mm) |
580*515*1250 |
650*610*1560 |
800*600*2060 |
1000*800*2060 |
2000*800*2060 |
3500*800*2060 |
6000*800*2060 |
||
|
Weight (kg) |
150 |
300 |
700 |
900 |
1300 |
2500 |
4500 |
||
1. Product introduction
The continuous development of economy has brought about a large amount of energy consumption. The energy crisis and environmental pollution are becoming increasingly serious. The development and large-scale application of new energy has become an inevitable trend of global energy applications. New energy power generation has the disadvantages of low energy density, instability and randomness. The development of energy storage technology can well solve the above problems, making it possible to apply new energy power generation on a large scale. Liquid flow battery is a new type of environment-friendly energy storage battery, which has the advantages of long service life and many times of charging, making it have broad market prospects in energy storage systems. The bidirectional energy storage converter is an energy conversion device between the energy storage battery and the power grid, so the research on the fluid flow energy storage bidirectional energy storage converter is of great significance.
2.Product principle
3. Product features
(1) High efficiency and energy saving: the highest efficiency can reach 95%, with a wide voltage input range, which can adapt to other types of batteries such as liquid flow batteries;
(2) Safe and reliable: multiple fault protection mechanism, real-time monitoring, ensuring safe, reliable and stable operation, supporting high and low voltage crossing, rapid power regulation, dynamic power compensation, and strong adaptability of the power grid;
(3) Super load carrying: the virtual synchronous operation technology is adopted, and the response is millisecond level, which can quickly withstand sudden load and equipment startup impact. The maximum short-term impact resistance is more than 3 times of the rated energy storage power, ranking first in the industry;
(4) Smart and friendly: through intelligent control start and stop technology, it supports multiple operation modes, parallel and off grid operation, new energy access, and grid connection of generator sets. In energy storage cooperation, the number of operating units can be adjusted according to the load.
4. Product application
It can be used as a backup power supply for communication facilities, military facilities, hospital buildings, residential areas and other occasions; Its excellent charging and discharging characteristics make it suitable for the power supply of electric vehicles; It can be used for power supply and energy storage in remote areas; At the same time, it can form an energy storage system with photovoltaic power generation and other new energy power generation systems to improve the power quality of the grid and adjust the peak valley difference of power consumption of the grid.
Technic parameter
|
Equipment model |
XNSX-50KS |
XNSX-100KS |
XNSX-250KS |
XNSX-500KS |
XNSX-1000KTL |
|
Rated power |
50kW |
100kW |
250kW |
500kW |
1000kW |
|
DC side parameters |
|||||
|
Maximum power |
55kW |
110kW |
275kW |
550kW |
1100kW |
|
DC charging voltage |
DC 0~800V |
||||
|
DC discharge voltage |
DC 50V~850V(Customizable) |
||||
|
Maximum |
200A |
400A |
1000A |
2000A |
4000A |
|
Ripple |
≤1% |
||||
|
AC side parameters (grid connection) |
|||||
|
Rated voltage |
AC 380V±15%,Three phase five wire system |
||||
|
Rated frequency |
50Hz |
||||
|
Total current |
THD<4% |
||||
|
power factor |
≥0.99 |
||||
|
AC side parameters (off grid) |
|||||
|
Rated voltage |
Line voltage AC 380V |
||||
|
Rated frequency |
50Hz |
||||
|
Output voltage |
<2%(linear load) |
||||
|
With unbalanced |
100% |
||||
|
Overload capacity |
120% 60s,150% 10s,200% 2s,300% Immediate protection |
||||
|
Efficiency |
|||||
|
Maximum efficiency |
95% |
98% |
|||
|
Protection function |
|||||
|
DC input protection |
Have |
||||
|
AC output protection |
Have |
||||
|
Overvoltage protection |
DC TypeⅡ/AC TypeⅡ |
||||
|
Island protection |
Have |
||||
|
Overheating protection |
Have |
||||
|
Other |
|||||
|
Isolation mode |
Built in isolation transformer |
No Isolation transformer |
|||
|
User interface |
LCD touch screen |
||||
|
Communication |
Ethernet/RS485 (MODBUS protocol) |
||||
|
High/low voltage |
Have |
||||
|
Degree |
IP20 |
||||
|
Working |
-20℃~45℃ |
||||
|
Relative |
0~95%(non condensing) |
||||
|
Cooling mode |
Forced air cooling |
||||
|
Operating |
2000m(derating over 2000m) |
||||
|
Dimension |
800*650*1940 |
1000*1000*2060 |
1800*1000*1900 |
2200*1000*2060 |
2400*1000*2060 |